AWG wire gauge chart.
Diameter, area, resistance, and ampacity for every common AWG size — from 4/0 down to 30. Sourced from ASTM B258 (geometry) and NEC Table 310.16 (ampacity).
The chart
| AWG | Diameter | Area | Resistance Ω / 1000 ft @ 20 °C |
Ampacity (NEC, Cu, 30 °C amb.) | ||||
|---|---|---|---|---|---|---|---|---|
| in | mm | mm² | kcmil | 60 °C | 75 °C | 90 °C | ||
Ampacity notes. Values are for copper conductors, not more than three current-carrying conductors in a raceway, at 30 °C ambient. The temperature column refers to the conductor insulation rating (TW = 60 °C, THW/RHW = 75 °C, THHN/XHHW = 90 °C). Derating factors apply for higher ambient temperatures or more conductors — see NEC §310.15(B). Aluminum is different; reduce by roughly one column (e.g., 10 AWG Al ampacity ≈ 12 AWG Cu).
Common applications
Practical wire gauges by use case. These are typical residential / light-commercial pairings, not a substitute for the NEC or your local code.
| Use case | Typical AWG | Why |
|---|---|---|
| Lamp / fixture wiring | 18, 16 | Low current (under 10 A), flexibility matters |
| Doorbells, thermostats | 18, 20 | Class 2 signaling, very low current |
| 15 A receptacles, lighting | 14 | Minimum for 15 A breaker per NEC |
| 20 A kitchen / bath circuits | 12 | Minimum for 20 A breaker per NEC |
| Electric dryer (30 A) | 10 | 30 A circuit @ 240 V |
| Electric range (40–50 A) | 8, 6 | Sized to breaker; 6 AWG common for 50 A |
| Subpanel feed (100 A) | 3, 2 | 2 AWG Cu @ 75 °C insulation |
| Main service entrance (200 A) | 2/0, 3/0 | 2/0 AWG Cu or 4/0 Al per NEC 310.12 |
| USB cable (data) | 28 | USB 2.0 spec; thicker pairs (24) for power |
| Speaker wire (typical run) | 16, 14 | 14 AWG for runs over 50 ft to keep loss low |
Common pitfalls
- Smaller number = bigger wire. 4/0 AWG is huge; 30 AWG is hair-thin. This trips up everyone the first time.
- AWG is not the same as metric gauge. Some old British and Asian wires use SWG (Standard Wire Gauge) which uses similar numbers but slightly different diameters. Don't substitute without checking.
- Stranded vs solid: a 12 AWG stranded conductor has a slightly smaller copper area than 12 AWG solid (typically about 5% less). The published AWG number refers to the total conductor cross-section.
- The ampacity column matters. The same 12 AWG wire can carry 20 A (with TW insulation) or 30 A (with THHN). Reading the column is the difference between a working circuit and a fire.
- Voltage drop, not ampacity, often governs long runs. For runs over 50 ft, size up for voltage drop even if ampacity allows the smaller wire. See the sizing calculator.
Common questions
Why does smaller AWG mean thicker wire?
AWG was originally based on the number of times a wire was drawn through progressively smaller dies — each pass made the wire thinner. So a 30-gauge wire was drawn 30 times (very thin), while 1-gauge was drawn only once (very thick). The number counts process steps, not size.
How do I size a wire for a 50-amp circuit?
Per NEC Table 310.16, 6 AWG copper at 75°C is rated 65 A and is the standard for a 50-amp circuit (NEC 80% derating rule: 65 × 0.8 = 52 A continuous). For aluminum, you'd step up to 4 AWG. Always check the specific code edition, the temperature rating of your terminals (60°C, 75°C, or 90°C), and the run length for voltage drop on long runs.
Is 12 AWG enough for 20 amps?
Yes, by NEC. 12 AWG copper has a 25 A ampacity at 60°C terminations and 30 A at 75°C, so a 20 A breaker is well within limit. The 80% continuous-load rule means it's actually rated for 24 A continuous at 60°C — comfortably above 20 A. Just confirm your terminations match the wire's temperature class.
What's the voltage drop on a 100-foot 12 AWG run?
For a 20 A load on 120 V at 100 ft round-trip (so 50 ft each way), 12 AWG copper has about 0.16 Ω resistance for the round trip. Voltage drop = 20 A × 0.16 Ω = 3.2 V, or 2.7%. NEC recommends keeping branch-circuit drop under 3%, so 12 AWG at 100 ft is right at the edge — bump to 10 AWG for longer runs or higher loads.
Can I run 14 AWG on a 20-amp breaker?
No. NEC requires 14 AWG to be on a maximum 15 A breaker, 12 AWG on max 20 A, and 10 AWG on max 30 A. The breaker protects the wire — if the breaker is rated higher than the wire ampacity, an overload won't trip the breaker before the wire heats. This is a fire hazard and a code violation.
Sources
- Geometry (diameter, area): ASTM B258 — Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors. Diameters computed from the formula d(n) = 0.005 × 92^((36−n)/39) inches.
- Resistance: Based on resistivity of annealed copper (1.7241 × 10⁻⁸ Ω·m at 20 °C, IEC 60228). Values given are for solid copper; stranded conductors are typically 2–4% higher.
- Ampacity: NFPA 70 (National Electrical Code), Table 310.16 — Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts. Values apply to copper conductors, not more than three current-carrying conductors in a raceway, at 30 °C ambient.
Disclaimer. This chart is provided for reference and educational use. Electrical installations must comply with the NEC and local codes; consult a licensed electrician for any installation you're not qualified to perform.
See also
Wire gauge calculator
Pick the right AWG given amperage, run length, voltage, and allowable voltage drop.
AWG ↔ mm² converter
Convert between American Wire Gauge and metric cross-sectional area.
Guide: AWG vs metric wire sizing
Why "smaller number = bigger wire," and the gotchas when sourcing internationally.